This product is a universal refrigeration with refrigerating capacity of 400W, it is improved from the cooling system of the instrument and equipment. This product is provided with a handle and one hand portable. Products can be equipped with anti-vibration base, without special installation, It can work when flatted on the water platform or ground.
①Small size and light weight: The weight of the whole machine is only 4.9kg, and the size is only 290mm (L) x 178mm (W) x 205mm (H), which can be carried by one person. | ②High efficiency: The refrigeration efficiency of the small micro refrigeration system is about 2, which is 5 times of the semiconductor refrigeration efficiency, and is far higher than other refrigeration and cooling methods. |
③Easy operation: The refrigerant connection and electrical connection of the product are both plugged by the quick connector. | ④High temperature control accuracy: The temperature can be manually set on the touch screen, and the product can achieve the temperature control accuracy of 1 degrees centigrade. |
⑤High reliability and safety: product development through a series of reliability and safety testing. The factory production of each product must go through the corresponding type test (vibration, pressure, high and low temperature environment, weather resistance, oil return, condensation, protection, liquid pump / fan components such as reliability, performance, electrical safety etc). | ⑥Good environmental adoptability: |
⑦High refrigerating capacity: When the ambient temperature is 30 degrees and the outlet water temperature is 20 degrees centigrade, the refrigerating capacity is 400W.The specific gas liquefaction ability is related to latent heat and specific heat capacity. |
NO. | Component Type | Component Name | Component Description |
---|---|---|---|
1 | Host | Compressor | Miniature DC variable frequency compressor |
2 | Evaporator | Micro-channel heat exchanger | |
3 | Condenser | Parallel flow micro-channel heat exchanger | |
4 | Cryogen | R134a Cryogen | |
5 | Display Panel | Touch panel | |
9 | Housing | Shell | Aluminum alloy shell,Surface anodic oxidation treatment |
10 | Power period or battery | Li-On rechargeable | Three yuan of lithium batteries |
11 | Charger | Battery adapter power supply |
Project | Unit | Value |
---|---|---|
Nominal refrigerating capacity | W | 400 |
Nominal power | W | 170 |
Host input voltage | V | DC20~26 |
Host rated current | A | 7 |
Host maximum current | A | 15 |
Range of output water temperature | °C | 5.0~35.0 |
Liquid work flow | L/s | 2.5 |
Maximum liquid supply pressure | kPa | 80 |
Liquid contact material | Polyether TPU、316L,ect,No copper and aluminum ions. | |
Exterior | mm | Long:290 |
Wide:178 | ||
High:205 | ||
Temperature control mode | Touch screen settings, host self-control | |
Working environment temperature | °C | -30~+55 |
Storage environment temperature | °C | -30~+70 |
Host Net Weight | kg | 4.9 |
Host noise | dB(A) | 57 |
Circulating medium | Distilled water or glycol antifreeze | |
Appearance material | ■Aluminum/ ■Silvery □Blue □Black □Others | |
Note: Nominal working condition: The ambient temperature is 35 degrees centigrade. The liquid temperature is 25 degrees centigrade. |
Project | Performance | Remarks |
---|---|---|
Nominal voltage | 22.2VDC | |
Working voltage | 19.0~25.2VDC | |
Nominal capacity | 6.5AH(Standard)or 10AH | |
Working temperature | Charge:0℃ ~45℃ | |
Discharge:-10℃~60℃ | ||
Storage temperature | 3 month:-20~45℃ | When stored, check regularly to keep the battery in power condition |
6 month:-20~30°C | ||
Net Weight | 0.9 or 1.4kg |
Input voltage range | AC 100-240V |
Rated input voltage | AC 220V |
Input frequency range | 47~63HZ |
Input current | 2.5A Max(@AC 180V,Full Load) |
Work efficiency | 85% Min(@220V AC,Full Load) |
Charging voltage | 25.2V DC |
Charging voltage range | 25.2~25.5V DC(Ref:25.3V DC@No Load) |
Charging current | 4.0A |
Working temperature | -30~45°C |
Storage temperature | -40~75°C |
Working humidity | 0~90% |
Storage humidity | 0~90% |
Cooling method | Natural air cooling |
LED Instructions | ||
---|---|---|
Charging state | Light (green) | Light (red) |
Waiting for charging | ON | OFF |
Plug in batteries | OFF | ON |
Charging completed | ON | OFF |
Output short circuit | FLASH | FLASH |
Output reverse connection protection | ON | OFF |
Note: The host will alarm for a long time beyond the operating range
Code | Fault | Code | Fault |
---|---|---|---|
F1 | Compressor overload/condenser fouling | F18 | Fan 4 overload |
F2 | Compressor self-protection | F21 | Disconnection of water pump |
F3 | Compressor communication failure | F22 | Pump overload / water filtration blockage |
F4 | High temperature protection of compressor | F26 | Environmental temperature sensor fault |
F11 | Fan 1 broken line | F27 | Liquid temperature sensor fault |
F12 | Fan 2 broken line | F28 | Fault of inlet temperature sensor |
F13 | Fan 3 broken line | F41 | Liquid or liquid flow is low |
F14 | Fan 1 overload | F42 | Environmental temperature anomaly |
F15 | Fan 2overload | F43 | Anti-freezing protection |
F16 | Fan 3 overload | F44 | Overvoltage/under voltage of power supply |
F17 | Fan 4 broken line | ||
Note:When some fault occurs, the host will continue to operate, but it will automatically take some recovery measures or alternative measures. |